3 medical incubators, constant temperature (ice) chambers, important pathological analysis and laboratory equipment; 4. Vacuum suction, compressor, oxygen concentrator;.
Each workstation in the consultation room is equipped with one double hole information socket, and an additional double hole information socket is installed in each consultation room;.
3. Two dual hole information sockets should be installed for registration, charging, dispensing, etc;.
When there are less than 2 medical inspection and examination equipment, one double hole information socket should be installed, and for every additional one, one single hole information socket should be added; The operator workstation and diagnostic report workstation should be equipped with one dual hole information socket at each workstation;.
Nurse stations in 5 nursing units should be equipped with 4 double hole information sockets;.
The office of the nursing unit director and head nurse should be equipped with 2 double hole information sockets;.
Each workstation in the 7 doctor’s office should be equipped with 2 dual hole information sockets; It is recommended to set up two dual hole information sockets in the display room of the nursing unit;.
One double hole information socket should be installed in other functional rooms of the nursing unit (including night doctor and nurse duty rooms);.
Each bedside bed should be equipped with one double hole information socket;.
Information sockets should be installed at the public entrances of nursing units on all floors;.
Public places within hospitals should be equipped with information sockets as needed;.
The data points required for the 13 information application systems are set as needed and are not included in the above items..
1. The boundary between medical and patient channels, pollution, and clean areas should be controlled, and entry and exit should be identified;.
The doors of the buffer room should have interlocking function and emergency unlocking function. In case of emergency, all doors with interlocking function should be in an openable state. The interlock door on the contaminated area side of the buffer room in the negative pressure isolation ward can only be opened after 1 minute of closing;.
For places with one-way entry and exit requirements, the entrance and exit control system should be in a one-way traffic state and have emergency unlocking function. In case of emergency, all doors of this place must be able to be opened;.
The entrance and exit controls set up on evacuation routes should be lifted in emergency situations, and all doors with interlocking functions should be in an openable state. All doors on evacuation routes should be in an openable state..
Reasonable functional zoning of buildings, clear flow lines for cleaning, medical and patient care, and personnel and vehicles are important measures to avoid cross infection;.
2 In order to cope with the possibility of epidemic spread, the infectious diseases Department of the General Hospital should reserve land for development, reconstruction and expansion..
1. The light switch is used for control, and the light switch is set in the corridor outside the door, with a height of 1.8m. A dedicated person is responsible for using specialized tools to open and manage the closure;.
2. Adopt dedicated circuits and centralized control, set control buttons in rooms with people on duty, and have a dedicated person operate and turn on the ultraviolet light when there is no one in the room;.
When conditions permit, intelligent control is used to detect the presence of people in the room, and the ultraviolet light is turned on by operating under two conditions: no one in the room and a fixed disinfection time..