The cause of the accident is still under further investigation.
Carry out pre job fire safety training for employees, and regularly organize fire safety training and fire drill.
Organize targeted fire drills.
The plant and warehouse should be set up separately and can not be mixed; The area and spacing of fire compartment shall meet the requirements of code for fire protection design of buildings; Fire separation shall be carried out between different use functions according to the categories with high risk.
Large smoke and strong toxicity.
After the fire, Jiashan County Party committee and county government immediately established a special disposal class to fully carry out fire fighting and on-site search and rescue.
For more highlights, please click the blue word above to follow us! At 16:06 on September 3, 2021, the workshop of Jiashan Shuangjie sponge Co., Ltd.
The inspection records shall be complete and accurate and filed for future reference.
Implement the fire safety responsibility system, formulate the fire safety system and fire safety operation procedures of the unit, and formulate fire fighting and emergency evacuation plans.
2.
Fire compartment shall be separated by firewall.
We remain neutral to the views in the text for reference and exchange only.
For underground or semi underground powerhouse (including underground or semi basement), the building area of each floor shall not be greater than 50m ², And the number of operators at the same time shall not exceed 15.
A comprehensive inspection shall be conducted on the building fire-fighting facilities at least once a year to ensure that they are intact and effective.
Main lessons (analyzed by the author): 1.
Smoldering is easy to occur.
Implement daily fire inspection and establish inspection records.
The safe evacuation distance, number and width of emergency exits of plants and warehouses shall meet the requirements of code for fire protection design of buildings.
There shall be no less than 2 emergency exits for each warehouse, and the floor area of a warehouse shall not be greater than 300m ² When, one emergency exit can be set.
Organize fire prevention inspection and eliminate potential fire hazards in time.
It can not only prevent fire, but also put out the initial fire and prevent small fire from becoming a disaster.
For each fire compartment or each floor of a fire compartment, the horizontal distance between the nearest edges of two adjacent emergency exits shall not be less than 5m.
The fire killed 6 enterprise personnel, the person in charge of the enterprise involved has been controlled by the police, and the aftermath work has been carried out simultaneously.
It is easy to cause fire and camp.
If it is a key fire control unit, it also needs to perform the following responsibilities: determine the fire safety manager and organize the implementation of the fire safety management of the unit.
Ensure that the evacuation passage, emergency exit and fire truck passage are unblocked, and ensure that the fire and smoke compartment and fire spacing meet the fire technical standards.
in Jiashan Development Zone, Jiaxing City, Zhejiang Province caught fire.
When the number of evacuees on each floor is not equal, the total net width of the evacuation stairs shall be calculated layer by layer, and the total net width of the lower stairs shall be calculated according to the number of evacuees on the floor and above with the largest number of evacuees.
Fast fire speed and high flame temperature.
For each fire compartment in the plant or each floor in a fire compartment, the number of emergency exits shall be calculated and determined, and shall not be less than 2; One emergency exit can be set when the following conditions are met: 1 class a plant, with a floor area of no more than 100m ², And the number of operators at the same time shall not exceed 5; 2 class B plant, with a floor area of no more than 150m ², And the number of operators at the same time shall not exceed 10; 3 class C plant, with a floor area of no more than 250m ², And the number of operators at the same time shall not exceed 20; 4.
The total net width of evacuation stairs, walkways and doors in the plant shall be calculated and determined according to the number of evacuees, and the minimum net width of evacuation per 100 people shall not be less than the provisions in table 3.7.5.
It is understood that the burning substances on site are waste paperboard and sponge.
Personnel stay in the building for a long time, evacuation time is long, and it is easy to inhale excessive toxic smoke.
[copyright belongs to the original author.
The total net width of the outer door on the first floor shall be calculated according to the number of evacuees on the floor and above, and the minimum net width of the door shall not be less than 1.20m.
The enterprise shall implement the main responsibility for fire safety and maintain its own fire safety: the enterprise shall set up a full-time or part-time fire safety management department to be responsible for its own fire safety management.
If the original author disagrees, please contact to delete.
Typical case 07:4906: training materials ● sorting out the setting requirements of smoke control system! ● summary of knowledge points on installation spacing, pipe diameter and pressure of fire-fighting facilities! ● summary of scrapping years of fire fighting equipment! ● construction process of smoke control and ventilation system [superfine] ● fire control room meets the standard! ● fire protection drawing identification method! Map reading is super simple! Disclaimer: the content of this number comes from the publicity of fire protection knowledge.
Configure fire-fighting facilities and equipment according to national and industrial standards, set fire safety signs, and regularly organize inspection and maintenance to ensure integrity and effectiveness.
Establish fire control archives, determine key parts of fire safety, set fire prevention signs and implement strict management.
Strengthen safety education and training for employees.
Thank the original author for sorting and sharing] Click “watching” and “like”!..
When the building area of the fire compartment is not greater than 100m ² When, one outlet can be set.
For class D and e plants, the building area of each floor shall not be greater than 400m ², And the number of operators at the same time shall not exceed 30; 5.
The emergency exits of the plant / warehouse shall be distributed.
Each fire compartment in the warehouse shall not have less than 2 exits leading to evacuation walkways, stairs or outdoor.
Main fire hazard of sponge: low ignition point.
3.
However, the minimum net width of evacuation stairs should not be less than 1.10M, the minimum net width of evacuation walkways should not be less than 1.40M, and the minimum net width of doors should not be less than 0.90M.
Doors leading to evacuation walkways or stairs shall be class B fire doors.
In order to prevent rain, additional awnings shall not be built to occupy the fire compartment, expand the fire compartment and change the safe evacuation environment.